Perform load calculations

00:01

In this video, we will cover specifying load classifications and defining demand factors.

00:10

In order for a component to be added to a circuit, the component must have an electrical connector.

00:18

Electrical connectors have several parameters that must be defined in order for Revit to properly calculate loads.

00:26

There are also several electrical settings that affect the way Revit calculates loads.

00:32

We'll take a look at how this works.

00:35

On the systems ribbon in the electrical panel, click the dialog box launcher to open the electrical settings dialog,

00:44

and then switch to the load calculations options.

00:50

There are two options for the apparent load calculation method.

00:55

Some true load and reactive load and some apparent load.

01:02

Revit defines the true load as the actual power used by the circuit and the apparent load is the real and reactive power used by the circuit.

01:14

You can select the option that works best for you and that method will be used for the entire project.

01:23

You can also create load classifications and demand factors,

01:31

in the load calculations options, click Load Classifications to open the load classifications dialogue.

01:38

Here, you can see the load classification types that have been created in the project.

01:45

When you select a type, you can see the name and abbreviation of what has been added, the demand factor and then the load class for use with spaces.

01:58

The important thing here is the demand factor.

02:02

When you expand the drop down, you can select one of the demand factors that have been created in the project.

02:09

You can also create new load classification types to meet the needs of your project.

02:17

I'll click Cancel and then click Demand Factors.

02:22

In the demand factors dialogue, you can see all the demand factor types.

02:28

Let's take a look at how demand factors are defined.

02:33

I'll click new and then accept the default name and click OK.

02:40

When defining demand factors, there are three calculation methods that you can use, constant by quantity and by load.

02:50

With constant selected you can then specify the constant demand factor.

02:56

You can also choose to add an additional load to the calculated result.

03:04

When you select by quantity, there are then two calculation options, total at 1 percentage and incrementally for each range.

03:15

You can also see an example below that.

03:18

And take note that the example does not correspond to what's been defined in the table.

03:23

The table is what you use to define the demand factor.

03:28

Let's take a look at how this works with total at 1 percentage selected.

03:33

I'll click the plus button two times to add two rows to the table.

03:40

You can then specify the values in the greater than column and the less than or equal to column.

03:47

For example, I'll input five in the first row for less than or equal to

03:53

and then I'll enter 10 in the second row and notice that the greater than column is updating.

03:59

As I'm updating the less than or equal to column.

04:03

It's also important to note that there are two options here, so greater than and then less than or equal to.

04:11

So it's important to keep that equal to in mind.

04:15

For the first row I'll enter 100% for the demand factor and the second row I'll enter 65% and then the third row I'll enter 50.

04:27

And so what we've done here is actually set up a table that will work for the example that's noted here,

04:33

and so if there are two items then all the loads will be calculated at 100%, and so two items is less than five, so our demand factor is 100%.

04:45

And then if 10 items are used, so in this case our second row here is greater than five and then less than or equal to 10.

04:53

And so if 10 items are used than the demand factor will be 65%.

04:59

So in other words, depending on the number of items, it'll fall into one of these rows and then that demand factor will be used for all loads.

05:07

So that's the important thing to note with total at 1percentage.

05:12

When you select incrementally for each range, then it changes.

05:16

And instead of being instead of a demand factor being used for all the loads, it will work incrementally.

05:24

And so if we have between zero and five, those first five will use a 100%,

05:29

and then between 6 and 10, those items will use 65% and then 11 or more will use 50%.

05:40

You'll also note that this example has changed and this does not.

05:45

The example here does not correspond to the table and so what I just explained was based off of the table that we created for the first example.

05:54

So don't worry about this example updating.

05:57

It's simply the same one for each option.

06:00

And just to give you an idea of how that works.

06:03

So either total at 1 percentage or incrementally.

06:07

The third calculation method is by load and by load works very similar.

06:12

There is a table that you can use to specify the demand factor and you can either select total at 1 percentage or incrementally for each range.

06:22

And instead of the quantity of items, we're looking at the load as indicated since by the by load calculation method,

06:33

okay, once again, you can add additional rows specify the greater than or the less than or equal to.

06:40

Once again pay attention to the fact that this is less than or equal to.

06:45

So that's a big thing when you're defining these and then with either of these, you can choose to add an additional load to the calculated result.

06:55

I will click cancel to close this dialog and then click cancel to close the electrical settings dialog.

07:02

Lastly, let's take a look at an electrical connector and those are defined in the family.

07:09

So also like the lighting fixture family.

07:11

And then click Edit Family, to open the lighting fixture family in the family editor and then select the electrical connector,

07:22

in the properties palette, you can see the system type and as long as one of the power options are selected, then we have several other options.

07:31

The important parameters I want to point out are the ones that we've just been covering.

07:35

And so the load classification, you can associate that to a family parameter.

07:42

That way you will have a parameter that you can modify in the project.

07:47

And so if the load classification of the connector was not mapped to a load classification parameter for the family,

07:56

then you would not be able to modify that.

07:59

And so if you if you notice that you're updating parameters in the family and it's not affecting your load,

08:04

then it's likely because one of the parameters for the electrical connector is not mapped appropriately.

08:12

You can also see the voltage and the number of poles.

08:16

In this case those parameters are not associated so they will be constant unless they're updated here in the family.

08:24

And then there's an apparent load phase 1, 2 and 3.

08:28

And for this example the Apparent Load Phase 1 is mapped to the apparent load family parameter, and then there's also a power factor parameter.

08:40

And so once again, any of those parameters can be associated to family parameters,

08:46

and then modified in either the family or in the project using that family parameter.

08:54

And so once again, depending on the electrical settings and your electrical connector parameter

09:01

parameters that will determine how Revit calculates the loads in your project.

Video transcript

00:01

In this video, we will cover specifying load classifications and defining demand factors.

00:10

In order for a component to be added to a circuit, the component must have an electrical connector.

00:18

Electrical connectors have several parameters that must be defined in order for Revit to properly calculate loads.

00:26

There are also several electrical settings that affect the way Revit calculates loads.

00:32

We'll take a look at how this works.

00:35

On the systems ribbon in the electrical panel, click the dialog box launcher to open the electrical settings dialog,

00:44

and then switch to the load calculations options.

00:50

There are two options for the apparent load calculation method.

00:55

Some true load and reactive load and some apparent load.

01:02

Revit defines the true load as the actual power used by the circuit and the apparent load is the real and reactive power used by the circuit.

01:14

You can select the option that works best for you and that method will be used for the entire project.

01:23

You can also create load classifications and demand factors,

01:31

in the load calculations options, click Load Classifications to open the load classifications dialogue.

01:38

Here, you can see the load classification types that have been created in the project.

01:45

When you select a type, you can see the name and abbreviation of what has been added, the demand factor and then the load class for use with spaces.

01:58

The important thing here is the demand factor.

02:02

When you expand the drop down, you can select one of the demand factors that have been created in the project.

02:09

You can also create new load classification types to meet the needs of your project.

02:17

I'll click Cancel and then click Demand Factors.

02:22

In the demand factors dialogue, you can see all the demand factor types.

02:28

Let's take a look at how demand factors are defined.

02:33

I'll click new and then accept the default name and click OK.

02:40

When defining demand factors, there are three calculation methods that you can use, constant by quantity and by load.

02:50

With constant selected you can then specify the constant demand factor.

02:56

You can also choose to add an additional load to the calculated result.

03:04

When you select by quantity, there are then two calculation options, total at 1 percentage and incrementally for each range.

03:15

You can also see an example below that.

03:18

And take note that the example does not correspond to what's been defined in the table.

03:23

The table is what you use to define the demand factor.

03:28

Let's take a look at how this works with total at 1 percentage selected.

03:33

I'll click the plus button two times to add two rows to the table.

03:40

You can then specify the values in the greater than column and the less than or equal to column.

03:47

For example, I'll input five in the first row for less than or equal to

03:53

and then I'll enter 10 in the second row and notice that the greater than column is updating.

03:59

As I'm updating the less than or equal to column.

04:03

It's also important to note that there are two options here, so greater than and then less than or equal to.

04:11

So it's important to keep that equal to in mind.

04:15

For the first row I'll enter 100% for the demand factor and the second row I'll enter 65% and then the third row I'll enter 50.

04:27

And so what we've done here is actually set up a table that will work for the example that's noted here,

04:33

and so if there are two items then all the loads will be calculated at 100%, and so two items is less than five, so our demand factor is 100%.

04:45

And then if 10 items are used, so in this case our second row here is greater than five and then less than or equal to 10.

04:53

And so if 10 items are used than the demand factor will be 65%.

04:59

So in other words, depending on the number of items, it'll fall into one of these rows and then that demand factor will be used for all loads.

05:07

So that's the important thing to note with total at 1percentage.

05:12

When you select incrementally for each range, then it changes.

05:16

And instead of being instead of a demand factor being used for all the loads, it will work incrementally.

05:24

And so if we have between zero and five, those first five will use a 100%,

05:29

and then between 6 and 10, those items will use 65% and then 11 or more will use 50%.

05:40

You'll also note that this example has changed and this does not.

05:45

The example here does not correspond to the table and so what I just explained was based off of the table that we created for the first example.

05:54

So don't worry about this example updating.

05:57

It's simply the same one for each option.

06:00

And just to give you an idea of how that works.

06:03

So either total at 1 percentage or incrementally.

06:07

The third calculation method is by load and by load works very similar.

06:12

There is a table that you can use to specify the demand factor and you can either select total at 1 percentage or incrementally for each range.

06:22

And instead of the quantity of items, we're looking at the load as indicated since by the by load calculation method,

06:33

okay, once again, you can add additional rows specify the greater than or the less than or equal to.

06:40

Once again pay attention to the fact that this is less than or equal to.

06:45

So that's a big thing when you're defining these and then with either of these, you can choose to add an additional load to the calculated result.

06:55

I will click cancel to close this dialog and then click cancel to close the electrical settings dialog.

07:02

Lastly, let's take a look at an electrical connector and those are defined in the family.

07:09

So also like the lighting fixture family.

07:11

And then click Edit Family, to open the lighting fixture family in the family editor and then select the electrical connector,

07:22

in the properties palette, you can see the system type and as long as one of the power options are selected, then we have several other options.

07:31

The important parameters I want to point out are the ones that we've just been covering.

07:35

And so the load classification, you can associate that to a family parameter.

07:42

That way you will have a parameter that you can modify in the project.

07:47

And so if the load classification of the connector was not mapped to a load classification parameter for the family,

07:56

then you would not be able to modify that.

07:59

And so if you if you notice that you're updating parameters in the family and it's not affecting your load,

08:04

then it's likely because one of the parameters for the electrical connector is not mapped appropriately.

08:12

You can also see the voltage and the number of poles.

08:16

In this case those parameters are not associated so they will be constant unless they're updated here in the family.

08:24

And then there's an apparent load phase 1, 2 and 3.

08:28

And for this example the Apparent Load Phase 1 is mapped to the apparent load family parameter, and then there's also a power factor parameter.

08:40

And so once again, any of those parameters can be associated to family parameters,

08:46

and then modified in either the family or in the project using that family parameter.

08:54

And so once again, depending on the electrical settings and your electrical connector parameter

09:01

parameters that will determine how Revit calculates the loads in your project.

Video quiz

What controls the demand factor used for an electrical connector?

(Select one)
Select an answer

1/1 questions left unanswered

Step-by-step guide

It appears you don't have a PDF plugin for this browser.

Was this information helpful?