














Transcript
00:01
In this video, we will cover specifying load classifications and defining demand factors.
00:10
In order for a component to be added to a circuit, the component must have an electrical connector.
00:18
Electrical connectors have several parameters that must be defined in order for Revit to properly calculate loads.
00:26
There are also several electrical settings that affect the way Revit calculates loads.
00:32
We'll take a look at how this works.
00:35
On the systems ribbon in the electrical panel, click the dialog box launcher to open the electrical settings dialog,
00:44
and then switch to the load calculations options.
00:50
There are two options for the apparent load calculation method.
00:55
Some true load and reactive load and some apparent load.
01:02
Revit defines the true load as the actual power used by the circuit and the apparent load is the real and reactive power used by the circuit.
01:14
You can select the option that works best for you and that method will be used for the entire project.
01:23
You can also create load classifications and demand factors,
01:31
in the load calculations options, click Load Classifications to open the load classifications dialogue.
01:38
Here, you can see the load classification types that have been created in the project.
01:45
When you select a type, you can see the name and abbreviation of what has been added, the demand factor and then the load class for use with spaces.
01:58
The important thing here is the demand factor.
02:02
When you expand the drop down, you can select one of the demand factors that have been created in the project.
02:09
You can also create new load classification types to meet the needs of your project.
02:17
I'll click Cancel and then click Demand Factors.
02:22
In the demand factors dialogue, you can see all the demand factor types.
02:28
Let's take a look at how demand factors are defined.
02:33
I'll click new and then accept the default name and click OK.
02:40
When defining demand factors, there are three calculation methods that you can use, constant by quantity and by load.
02:50
With constant selected you can then specify the constant demand factor.
02:56
You can also choose to add an additional load to the calculated result.
03:04
When you select by quantity, there are then two calculation options, total at 1 percentage and incrementally for each range.
03:15
You can also see an example below that.
03:18
And take note that the example does not correspond to what's been defined in the table.
03:23
The table is what you use to define the demand factor.
03:28
Let's take a look at how this works with total at 1 percentage selected.
03:33
I'll click the plus button two times to add two rows to the table.
03:40
You can then specify the values in the greater than column and the less than or equal to column.
03:47
For example, I'll input five in the first row for less than or equal to
03:53
and then I'll enter 10 in the second row and notice that the greater than column is updating.
03:59
As I'm updating the less than or equal to column.
04:03
It's also important to note that there are two options here, so greater than and then less than or equal to.
04:11
So it's important to keep that equal to in mind.
04:15
For the first row I'll enter 100% for the demand factor and the second row I'll enter 65% and then the third row I'll enter 50.
04:27
And so what we've done here is actually set up a table that will work for the example that's noted here,
04:33
and so if there are two items then all the loads will be calculated at 100%, and so two items is less than five, so our demand factor is 100%.
04:45
And then if 10 items are used, so in this case our second row here is greater than five and then less than or equal to 10.
04:53
And so if 10 items are used than the demand factor will be 65%.
04:59
So in other words, depending on the number of items, it'll fall into one of these rows and then that demand factor will be used for all loads.
05:07
So that's the important thing to note with total at 1percentage.
05:12
When you select incrementally for each range, then it changes.
05:16
And instead of being instead of a demand factor being used for all the loads, it will work incrementally.
05:24
And so if we have between zero and five, those first five will use a 100%,
05:29
and then between 6 and 10, those items will use 65% and then 11 or more will use 50%.
05:40
You'll also note that this example has changed and this does not.
05:45
The example here does not correspond to the table and so what I just explained was based off of the table that we created for the first example.
05:54
So don't worry about this example updating.
05:57
It's simply the same one for each option.
06:00
And just to give you an idea of how that works.
06:03
So either total at 1 percentage or incrementally.
06:07
The third calculation method is by load and by load works very similar.
06:12
There is a table that you can use to specify the demand factor and you can either select total at 1 percentage or incrementally for each range.
06:22
And instead of the quantity of items, we're looking at the load as indicated since by the by load calculation method,
06:33
okay, once again, you can add additional rows specify the greater than or the less than or equal to.
06:40
Once again pay attention to the fact that this is less than or equal to.
06:45
So that's a big thing when you're defining these and then with either of these, you can choose to add an additional load to the calculated result.
06:55
I will click cancel to close this dialog and then click cancel to close the electrical settings dialog.
07:02
Lastly, let's take a look at an electrical connector and those are defined in the family.
07:09
So also like the lighting fixture family.
07:11
And then click Edit Family, to open the lighting fixture family in the family editor and then select the electrical connector,
07:22
in the properties palette, you can see the system type and as long as one of the power options are selected, then we have several other options.
07:31
The important parameters I want to point out are the ones that we've just been covering.
07:35
And so the load classification, you can associate that to a family parameter.
07:42
That way you will have a parameter that you can modify in the project.
07:47
And so if the load classification of the connector was not mapped to a load classification parameter for the family,
07:56
then you would not be able to modify that.
07:59
And so if you if you notice that you're updating parameters in the family and it's not affecting your load,
08:04
then it's likely because one of the parameters for the electrical connector is not mapped appropriately.
08:12
You can also see the voltage and the number of poles.
08:16
In this case those parameters are not associated so they will be constant unless they're updated here in the family.
08:24
And then there's an apparent load phase 1, 2 and 3.
08:28
And for this example the Apparent Load Phase 1 is mapped to the apparent load family parameter, and then there's also a power factor parameter.
08:40
And so once again, any of those parameters can be associated to family parameters,
08:46
and then modified in either the family or in the project using that family parameter.
08:54
And so once again, depending on the electrical settings and your electrical connector parameter
09:01
parameters that will determine how Revit calculates the loads in your project.
00:01
In this video, we will cover specifying load classifications and defining demand factors.
00:10
In order for a component to be added to a circuit, the component must have an electrical connector.
00:18
Electrical connectors have several parameters that must be defined in order for Revit to properly calculate loads.
00:26
There are also several electrical settings that affect the way Revit calculates loads.
00:32
We'll take a look at how this works.
00:35
On the systems ribbon in the electrical panel, click the dialog box launcher to open the electrical settings dialog,
00:44
and then switch to the load calculations options.
00:50
There are two options for the apparent load calculation method.
00:55
Some true load and reactive load and some apparent load.
01:02
Revit defines the true load as the actual power used by the circuit and the apparent load is the real and reactive power used by the circuit.
01:14
You can select the option that works best for you and that method will be used for the entire project.
01:23
You can also create load classifications and demand factors,
01:31
in the load calculations options, click Load Classifications to open the load classifications dialogue.
01:38
Here, you can see the load classification types that have been created in the project.
01:45
When you select a type, you can see the name and abbreviation of what has been added, the demand factor and then the load class for use with spaces.
01:58
The important thing here is the demand factor.
02:02
When you expand the drop down, you can select one of the demand factors that have been created in the project.
02:09
You can also create new load classification types to meet the needs of your project.
02:17
I'll click Cancel and then click Demand Factors.
02:22
In the demand factors dialogue, you can see all the demand factor types.
02:28
Let's take a look at how demand factors are defined.
02:33
I'll click new and then accept the default name and click OK.
02:40
When defining demand factors, there are three calculation methods that you can use, constant by quantity and by load.
02:50
With constant selected you can then specify the constant demand factor.
02:56
You can also choose to add an additional load to the calculated result.
03:04
When you select by quantity, there are then two calculation options, total at 1 percentage and incrementally for each range.
03:15
You can also see an example below that.
03:18
And take note that the example does not correspond to what's been defined in the table.
03:23
The table is what you use to define the demand factor.
03:28
Let's take a look at how this works with total at 1 percentage selected.
03:33
I'll click the plus button two times to add two rows to the table.
03:40
You can then specify the values in the greater than column and the less than or equal to column.
03:47
For example, I'll input five in the first row for less than or equal to
03:53
and then I'll enter 10 in the second row and notice that the greater than column is updating.
03:59
As I'm updating the less than or equal to column.
04:03
It's also important to note that there are two options here, so greater than and then less than or equal to.
04:11
So it's important to keep that equal to in mind.
04:15
For the first row I'll enter 100% for the demand factor and the second row I'll enter 65% and then the third row I'll enter 50.
04:27
And so what we've done here is actually set up a table that will work for the example that's noted here,
04:33
and so if there are two items then all the loads will be calculated at 100%, and so two items is less than five, so our demand factor is 100%.
04:45
And then if 10 items are used, so in this case our second row here is greater than five and then less than or equal to 10.
04:53
And so if 10 items are used than the demand factor will be 65%.
04:59
So in other words, depending on the number of items, it'll fall into one of these rows and then that demand factor will be used for all loads.
05:07
So that's the important thing to note with total at 1percentage.
05:12
When you select incrementally for each range, then it changes.
05:16
And instead of being instead of a demand factor being used for all the loads, it will work incrementally.
05:24
And so if we have between zero and five, those first five will use a 100%,
05:29
and then between 6 and 10, those items will use 65% and then 11 or more will use 50%.
05:40
You'll also note that this example has changed and this does not.
05:45
The example here does not correspond to the table and so what I just explained was based off of the table that we created for the first example.
05:54
So don't worry about this example updating.
05:57
It's simply the same one for each option.
06:00
And just to give you an idea of how that works.
06:03
So either total at 1 percentage or incrementally.
06:07
The third calculation method is by load and by load works very similar.
06:12
There is a table that you can use to specify the demand factor and you can either select total at 1 percentage or incrementally for each range.
06:22
And instead of the quantity of items, we're looking at the load as indicated since by the by load calculation method,
06:33
okay, once again, you can add additional rows specify the greater than or the less than or equal to.
06:40
Once again pay attention to the fact that this is less than or equal to.
06:45
So that's a big thing when you're defining these and then with either of these, you can choose to add an additional load to the calculated result.
06:55
I will click cancel to close this dialog and then click cancel to close the electrical settings dialog.
07:02
Lastly, let's take a look at an electrical connector and those are defined in the family.
07:09
So also like the lighting fixture family.
07:11
And then click Edit Family, to open the lighting fixture family in the family editor and then select the electrical connector,
07:22
in the properties palette, you can see the system type and as long as one of the power options are selected, then we have several other options.
07:31
The important parameters I want to point out are the ones that we've just been covering.
07:35
And so the load classification, you can associate that to a family parameter.
07:42
That way you will have a parameter that you can modify in the project.
07:47
And so if the load classification of the connector was not mapped to a load classification parameter for the family,
07:56
then you would not be able to modify that.
07:59
And so if you if you notice that you're updating parameters in the family and it's not affecting your load,
08:04
then it's likely because one of the parameters for the electrical connector is not mapped appropriately.
08:12
You can also see the voltage and the number of poles.
08:16
In this case those parameters are not associated so they will be constant unless they're updated here in the family.
08:24
And then there's an apparent load phase 1, 2 and 3.
08:28
And for this example the Apparent Load Phase 1 is mapped to the apparent load family parameter, and then there's also a power factor parameter.
08:40
And so once again, any of those parameters can be associated to family parameters,
08:46
and then modified in either the family or in the project using that family parameter.
08:54
And so once again, depending on the electrical settings and your electrical connector parameter
09:01
parameters that will determine how Revit calculates the loads in your project.
Step-by-step guide